Ventilation & Smoke Extraction
Fire protection requirements for ventilation ducts are directly related to their design function, the nature and behaviour of the fire and the construction materials that fuel the fire load. The fire resistance performance of the ventilation duct itself also plays a critical role. It is possible to prevent fire spread from one fire compartment (e.g. between floors) to another, along stairways and general access corridors only if all building materials and structural elements share a common fire classification and fire resistance rating. Typical steel sheet ducts fail to meet internationally accepted fire protection requirements. They heat and deform rapidly from the effects of fire. In certain circumstances they even accelerate the spread of flame and smoke.
Ventilation ducts up to 120 minutes fire resistance
Sheet steel ducts from an independent manufacturer can be cladded with PROMATECT® fire protection boards or the duct can be fabricated entirely from PROMATECT® fire protection boards.
When existing steel sheet ducts are cladded, for example, with PROMATECT® fire protection boards it is necessary to satisfy additional fire protection requirements for change in use status.
Ventilation ducts are tested according to EN 1366-1 and classified according to EN 13501-3. The classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both. Promat solutions in both cases (with or without steel ducts) fulfil the requirements from both sides ‘(i ↔ o)’.
A more economical solution, however, is achieved by specifying and installing tested and proven PROMATECT® ventilation ducts from Promat, the world leader in professional fire science technologies.
Heat and smoke control ducts up to 120 minutes fire resistance
The smoke extraction lines are tested automatically with fire load from both sides.Basically two heat and smoke control ducts can be distinguished:
- single compartment smoke control ducts, which can be used in one fire section only and are tested according to EN 1366-9 and classified according to EN 13501-4
- multi compartment fire resistant smoke control ducts, which can be used in any number of fire sections and are tested according to EN 1366-8 and classified according to EN 13501-4
Promat offers solutions without steel ducts for both systems up to 120 minutes fabricated with PROMATECT® fire protection boards.
Downloads
Технічна підтримка
Зверніться до нашої команди технічної підтримки, щоб отримати відповіді на запитання щодо пасивних рішень протипожежного захисту, наших продуктів та систем.
Технічна документація
Знайдіть всі необхідні сертифікати, таблиці даних про продукцію, експлуатаційні характеристики та інші документи, необхідні для вашої роботи